Polyisocyanurate Insulation
Specification
Physical Properties
Data Sheet (PDF)
MSDS
Approvals and Compliance
Recommended Thicknesses
Installation
Size and Dimension

ISO-C1 Installation Guidelines

SCOPE: This Installation Guide Provides Recommended Materials and Installation Practices for ISO-C1 Insulation Manufactured by Dyplast Products in the following applications:

  • piping
  • vessels and other equipment
  • process ducts

For Specifications in accordance with 3-part Construction Specification Institute (CSI) format, view www.dyplastproducts.com/index_specs.htm.

Click here for a downloadable Adobe Acrobat format (.pdf) file (600 kb)

Click here for a downloadable MicroSoft Word (.doc) file (1.9 mb)

Physical Characteristics of dP ISO Rigid Foam Polyisocyanurate Insulation:

  • A complete list of physical properties can be found by viewing www.dyplastproducts.com/index_physical_prop.htm.
  • ISO-C1 meets Class 1 flame spread and smoke density
  • A suffix following the ISO-C1brand as "Series 200, 300, 400, or 600" indicates densities of 2, 3, 4 or 6 pounds, respectively.
  • ISO products can be used to insulate systems operating from – 297F to + 300F (- 183C to + 149C).
  • ISO products are free of CFC and HCFC blowing agents
  • Excellent moisture vapor resistance, >90% closed cell (2 perm inches/ASTM C209).
  • ISO-C1is manufactured as bunstock and can fabricated to virtually any size and configuration
  • ISO-C1meets or exceeds the requirements according to ASTM C591.
  • ISO-C1thermal resistance is R=6.67 at 1 inch thick per ASTM C518 (k=0.15); with the product conditioned for 6 months at 70-75F and 45-55% RH prior to testing the R=5.6 (k=0.18).
  • ISO-C1 has high compressive strength, is light weight and easy to install.

Limitations and Disclaimer of Warranties and Liabilities

Important: The statements expressed on these pages are the general recommendations for the application of the products as outlined, and written for the interpretation and application by an experienced contractor.  Any deviation from these recommended procedures shall be at the sole risk of the installers. Failure to follow these instructions may result in serious damage to the application and life of this roofing product, resulting in the termination of any warranty, expressed or implied.  Characteristics, properties, performance of materials, and application specifications herein described are based on data obtained under controlled conditions.

Information is supplied upon the condition that the persons receiving same will make their own determination as to its suitability for their purposes and the reasonableness of the recommendations under the actual installation circumstances.  Dyplast Products makes no implied warranties of any type, including without limitation, any warrant of merchantability or fitness of purpose. In no event will Dyplast Products be responsible for damages of any nature whatsoever resulting from the use of or reliance upon this information or the product to which information refers. No agent, sales representative, or employee is empowered to change, alter, or amend this provision, unless approved in writing by a duly authorized officer of Dyplast Products.

          

Table of Contents

SCOPE

Applicability

This guideline covers the installation of ISO-C1 Rigid Polyisocyanurate Insulation on Liquefied Natural Gas (LNG) piping systems, tanks, vessels and equipment. Due to the variations in service conditions and use, this guideline may not be pertinent for every application. A design or specifying engineer can create specifications tailored to particular applications or owner’s needs. Such a design or specification engineering service may be more familiar with local conditions, budgets, environment, and desired service life of the system allowing them to generate a precise specification. While supplemental insulation products may be referenced in this guideline, Dyplast recommends consulting the manufacturers of these products for proper installation and handling.

Dyplast References

Product data sheets and other Dyplast literature are referenced throughout this guideline. Visit www.DyplastProducts.com for the latest version of these documents. The information contained in this guideline and referenced Dyplast documents are current as of January 2007. This guideline is subject to revision without notice. Visit www.DyplastProducts.com for the latest version of this document.

No Warranty

This guideline is offered as a guide for the purpose described herein. No warranty of procedures, either expressed or implied is intended. All other express or implied warranties of merchantability or fitness for a particular purpose are disclaimed.

 

GENERAL

Clean Piping

All piping shall be free of foreign substances and free of surface moisture or frost prior to the application of insulation.

Shipping/Storage

All insulation material shall be delivered to the project site in original, unbroken factory packaging labeled with product designation and thickness. The shipping package should not be air-tight. Shipment of materials from the manufacturer to the installation location shall be in weather-tight transportation. Insulation materials delivered to the job-site shall be stored so as to protect the materials from moisture and weather during storage and installation. Insulation material shall be protected from sunlight to avoid exposure to UV light from the sun.

Testing

All testing of piping systems shall be completed prior to the installation of the insulation system.

Thickness

Refer to insulation thickness charts in Appendix C for recommended insulation thickness based on specific design criteria. For additional insulation thickness calculations utilize the 3E Plus program available at http://www.pipeinsulation.org.

 

MATERIALS OF CONSTRUCTION

Insulation Materials For Piping, Fittings, And Valves

Insulation shall be ISO-C1 2500 and/or 3000 Rigid Polyisocyanurate Insulation manufactured by Dyplast Products.

Insulation shall have a maximum aged thermal conductivity of 0.18 BTU-in/hr-ft2-°F (0.025 W/m-°C) at 75°F mean.

Applications of 2 lb/ft2 density polysio requiring Class 1 (ISO-C1/2.0) ratings per ASTM E84 shall have UL classifications and FM specifications and shall have been tested and audited by an independent laboratory.

 

Fabrication Of Insulation

Insulation shall be fabricated in required shapes from bun stock in accordance with ASTM C-450 “Standard Practice for Prefabrication and Field Fabrication of Thermal Insulating Fitting Covers for NPS Piping, Vessel Lagging, and Dished Head Segments” and C-585 “Standard Practice for Inner and Outer Diameters of Rigid Thermal Insulation for Nominal Sizes of Pipe and Tubing (NPS System)”. Insulation shall be factory fabricated from bun stock.

Fittings, such as valves, valve stations, flanges, 90° and 45° elbows, and tees shall be two piece flycut or routed as the preferred fabrication method. For diameters too large for flycutting or routing, the pieces shall be fabricated in two halves with each half made up of mitered sections. Both methods shall be in accordance with ASTM C-450 and ASTM C-585. Refer to applications sections 4.1.6 and 4.1.7 for related additional information.

Store the bun stock at normal shop (indoor) conditions for at least 24 hours before fabrication. This will allow the ISO-C1 bun stock to equilibrate to the shop conditions. For best fabrication quality, it is recommended that ISO-C1 buns be fabricated into pipe shells in conveyor direction (length direction) to maximize flatness. For factory applied vapor retarder, the fabricated pipe shells shall be aged for 24 hours before vapor retarder attachment. Similarly after fabrication of the fittings/elbows/tees, allow the cut pieces to age for 24 hours before factory application of the vapor retarder to the fabricated pieces. After application of vapor retarder, fabricated pipe shells shall not be stored for more than one month either in the warehouse or at a job site.

Adhesives, Joint Sealers And Mastics

Solvent based adhesives, joint sealers and mastics may be used in contact with ISO-C1 insulation. Mastics shall remain flexible at the lowest expected ambient temperature.

Joint sealers for sealing joints of insulation shall be vapor retarder type, moisture and water resistant, non hardening, and flexible with a service temperature range from -275°F to +200°F.

A vapor retarder type joint sealer shall be applied on insulation longitudinal joints and butt joints to prevent moisture and moisture vapor infiltration. Such joint sealers are Fosters 95-50 sealer or approved equal. Please consult joint sealer manufacturer for recommended products

Solvent or water adhesives may be used to attach the vapor barrier to the outer surface of the ISO-C1. Refer to the vapor barrier installation guidelines. Consult adhesive manufacturer's literature for instructions on handling adhesives including required operating temperatures. Potential adhesives for use in this application include:

a) Childers CP 88 adhesive (solvent based)

b) Foster 81-05 adhesive (solvent based)

c) Foster 85-50 adhesive (water based)

d) Foster 85-60 adhesive (water based)

Vapor Retarder

A double layer vapor retarder design shall be used for LNG applications. The secondary vapor retarder shall be applied between the outer most foam insulation layer and the next inner layer of foam insulation. A primary vapor retarder shall be applied to the outer most foam insulation layer. Refer to Figure 2 in Appendix B for details.

Vapor retarder shall be Insulrap 50 Laminated Vapor Retarder for Pipe Insulation, Saran 560 Vapor Retarder Film or Equal. Refer to ASTM standards C-755 and C-1136 for information on selection and specification of vapor retarders. Refer to product literature and installation guidelines from the vapor retarder manufacturer for recommended application instructions.

Elbows and fittings shall be wrapped with vapor retarder tape with a 50% overlap.

Vapor Retarder shall have a maximum permeance of 0.01 perm.

For other laminated membrane type vapor retarders, consult manufacturer’s literature and installation guidelines.

Vapor retarder may be factory or field applied to the outer surface of pipe insulation.

For tanks, vessels, and equipment, use similar Vapor Retarder Films or approved equal.

Contraction/Expansion Joints

The location of contraction/expansion joints should be determined considering the expected pipe movements.

Contraction/expansion joints should be installed in the inner insulations layers of the horizontal piping and equipment.

The joints should be installed at maximum intervals of 20 feet. Consult with the appropriate engineer to determine the proper spacing of the contraction/expansion joints for each system.

Contraction/expansion joints should be filled with a resilient mineral fiber or approve alternate with fibers oriented parallel to the direction of the pipe. The contraction/expansion joint filler should be twice the thickness of the contraction/expansion joint (compressed to _ the thickness). Consult with the appropriate engineer to determine the proper contraction/expansion filler material.

Protective Jacketing Material

Shall be one of the following:

A) Aluminum Sheet

Jacketing shall be aluminum alloys 3003, 1100 or 3105, H-14 temper, meeting ASTM B-209. Use white painted aluminum jacketing for all outdoor applications. Consult jacketing manufacturer for recommended thicknesses. Typical thickness is 0.016” (up to 24” pipe) and 0.024” (> 24” pipe size).

Aluminum jacketing for all fittings, tees, elbows, valves, caps, etc. shall be sectional, factory contoured, or field-fabricated to fit closely around insulation.

Banding for jacketing shall be 0.02" thick by 1/2" wide stainless steel.

Aluminum protective jacketing shall not be considered a vapor retarder. See section 3.4 for vapor retarder recommendations.

No fastener capable of penetrating the underlying vapor retarder shall be used to secure the aluminum jacket.

 

B) Stainless Steel

The material shall be of a quality meeting the requirements of ASTM A167 Type 304. Use white painted stainless steel jacketing for all outdoor applications. Consult jacketing manufacturer for recommended thicknesses.

Banding for jacketing shall be 0.02" thick by 1/2" wide stainless steel.

Stainless steel protective jacketing shall not be considered a vapor retarder. See section 3.4 for vapor retarder recommendations.

No fastener capable of penetrating the underlying vapor retarder shall be used to secure the stainless steel jacket.

APPLICATION

Piping – General

All piping, operating at LNG temperatures, requiring 5” or more of insulations shall be applied in three layers. Comprising of an inner, middle, and outer layer of ISO-C1 insulation. See Table 1 in Appendix B for details.

All piping, operating at LNG temperatures, requiring less than 5” of insulations shall be applied in two layers. Comprising of an inner and outer layer of ISO-C1 insulation. See Table 1 in Appendix B for details.

Where insulation thickness required is less than 5”, utilize a double layer system. Stagger all longitudinal joints between the inner and outer layers. Install the inner and outer layer longitudinal joints 90° to each other with the inner layer joints in the 12 and 6 o’clock positions and the outer layer joints in the 3 and 9 o’clock positions. All butt joints between the inner and outer layers shall be staggered between 6 and 18 inches. Refer to Figure 1 in Appendix B.

Where insulation thickness required is greater than 5”, utilize a triple layer system. Stagger all longitudinal joints between the inner, middle, and outer layers. Install the inner, middle, and outer layer longitudinal joints 90° to each other with the inner layer joints in the 3 and 9 o’clock positions, the middle layer joints in the 12 and 6 o’clock positions, and the outer layer joints in the 3 and 9 o’clock positions. All butt joints between the inner, middle and outer layers shall be staggered between 6 and 18 inches. Refer to Figure 2 in Appendix B.

Insulation shall be fabricated with shiplap or tongue and groove longitudinal joints and shiplap ends.

Install pre-fabricated insulation fittings on elbows, tees, and valves. Insulation shall be the same thickness as pipe sections and fabricated with shiplap ends and shiplap or tongue and groove longitudinal joints. Refer to Figure 3 in Appendix B

In a triple layer insulation system, the inner layer shall not be installed with sealants. In triple layer systems the inner, middle and outer layer shall remain independent of each other so as to allow movement between the layers.

In double layer insulation system, inner layer shall not be installed with sealants. In double layer systems the inner and outer layer shall remain independent of each other to allow movement between the layers. Refer to Figure 1 in appendix B.

Insulation shall be secured to the pipe with 3/4" wide fiber reinforced tape. Tape shall be applied as per Figure 4 in Appendix B.

Insulation shall be secured with fiber reinforced tape on both inner and outer layers of a multi layered systems except as noted in section 4.1.13.

Insulation shall be secured with fiber reinforced tape prior to installation of the vapor retarder material when vapor retarder is field applied.

Outer layer insulation and vapor retarder shall be secured with fiber reinforced tape. Use a 25% circumferential overlap on 12” centers when vapor retarder is factory applied to insulation. Fiber tape shall be applied to the exterior of the insulation/vapor retarder system.

Contraction/expansion joints shall be installed as described in section 3.5 and illustrated in Figure 5 in Appendix B or approved alternate design. The appropriate designer or engineer must specify the spacing of contraction/expansion joints separately for each system.

All insulation shall be tightly butted and free of voids and gaps at all joints. Vapor retarder must be continuous. All fasteners and bands shall be neatly aligned and overall work must be of high quality appearance and workmanship.

Vapor stops shall be used on either side of valves frequently removed for servicing, valve stations left exposed, or odd fittings, elbows, tees, etc. where the chance of moisture infiltration is high. Install per detail in Figure 6 in Appendix B or an approved alternate design.

Vapor Retarder Film to be cut to length longitudinally and wrapped around the circumference of the pipe with lap joint facing downward avoiding the placement of the joint at the top or bottom of the pipe. Lap joint to be sealed using liquid adhesive. Butt joints shall be covered with Vapor Retarder Tape. Spiral wrap configuration can be used in lieu of the above installation. Spiral wrapping will require adhesive placed on one edge of the vapor retarder as it is wrapped over the previous layer.

Elbows and fittings shall be wrapped with Vapor Retarder Tape or covered with a mastic type vapor retarder product. Vapor Retarder Tape is to be wrapped in a spiral configuration. If using mastic type vapor retarder at fittings and elbows, form mastic so that fitting covers can be applied true and tight.

On factory applied Vapor Retarder Film, lap joint to be sealed with SSL tape. All vapor retarder surfaces should be cleaned and free of dust, grease, oil, etc before application of the SSL tape to ensure good adhesion between the tape and vapor retarder. Refer to Figure 7 in Appendix. For other types of factory applied vapor retarders, consult manufacturer’s recommendations on installation.

Before jacketing can be installed on a portion of the piping, the vapor retarder system on that portion must be complete and continuous.

Its good engineering practices to coat the pipes in LNG applications. Consult Appendix A for conditions where pipe coating systems are suggested.

 

Outdoor Piping

This section covers outdoor areas including, but not limited to, process areas, rooftops and rooftop equipment.

ISO-C1 Insulation shall be protected from prolonged exposure to UV light and weather upon installation.

Outdoors, insulation materials shall be covered with a jacketing material within two weeks of installation to eliminate long-term exposure to UV light.

Refer to section 3.6 for material specification on outdoor jacketing.

Outdoor jacketing overlap shall be a minimum of 2" at butt joints and a minimum of 2” at longitudinal joints. Jacketing shall be caulked before closing and banding and positioned in an orientation to avoid water infiltration.

Straight sections of jacketing shall be neatly secured with bands and seals with a maximum spacing of 9" on center. End joints shall be secured with bands and seals centered directly over joint. Do not use screws, staples or other fasteners on lines containing a vapor retarder system.

 

Tank, Vessel, and Equipment Insulation

All insulation materials shall be the same as those used on the pipe associated with the tank, vessel, or equipment.

Tank and vessel head segments shall be curved cut to fit in single piece or segments per ASTM C-450. Head segments shall be cut so as to eliminate voids at the head section and in a minimum number of pieces so as to eliminate through joints.

Curved segments shall be fabricated to fit the contour of the surface in equal size pieces to go around the vessel with a minimum number of through joints. Cutting in the field shall be minimized. All sections shall be tightly butted and free of voids and gaps.

Vertical vessels greater than 4 feet in diameter require an insulation support ring welded or bolted around the bottom of the tank to prevent the shell insulation from sliding down.

Seal all outer layer and single layer butt joints with joint sealer. Refer to section 3.3.

In multi layer applications, the horizontal and vertical joints of the inner and outer layer curved segments shall be staggered (see Figure 8 in Appendix B).

The top of the outer layer of wall insulation in a multi layer system shall be held below the inner layer top a minimum of the insulation thickness. The tank head insulation layers shall be cut so as to meet the staggered joint.

Secure the shell insulation with stainless steel bands on 12 inch centers.

Install Vapor Retarder Film. Tightly wrap the vessel or equipment insulation circumferentially with vapor retarder film. Overlap the seams by a minimum of 2 inches. Seal the overlapped seams with vapor retarder tape. On vertical vessels apply the vapor retarder film starting with the bottom course and work upwards. Each course should overlap on top of the one below it thus providing a joint that will naturally shed water.

The vapor retarder on curved head sections shall be mastic/fab/mastic or approved alternate. Flat head sections can be covered with vapor retarder film. Lap joints shall be covered with Vapor Retarder Tape.

Legs and appendages attached directly to the shell shall be insulated out from the vessel head or wall four times the insulation thickness and the insulation termination sealed with a vapor stop.

On outdoor equipment use aluminum jacketing per section 3.5. Rivets and screws shall not be used to attach jacketing on systems using a vapor retarder.


 

APPENDICES

APPENDIX A: CORROSION RESISTANT METAL COATINGS

GENERAL NOTE: Corrosion of metal pipe, vessels, and equipment under insulation, while not typically caused by the insulation, is still a significant issue that must be considered during the design of any mechanical insulation system. The propensity for corrosion is dependent on many factors including the ambient environment and the operating temperature of the metal. The recommendations below represent the general practice in the industry but are not meant to take the place of proper system design and specification by a qualified design engineer familiar with this type of construction. We recommend that the owner consult such an engineer and have them work closely with the fabricator, the contractor, and Dyplast to help insure a properly designed, installed, and long-lasting insulation system free of corrosion.

SPECIFIC RECOMMENDATIONS:

5.1.2.1 Stainless Steel All 300 series stainless steel shall be coated with an epoxy primer at 5 mil thickness and an epoxy finish coat at 5 mil thickness if operating in a temperature range between 140°F and 300°F or if in a cycling temperature service where the service temperature is between 140° and 300°F for more than 20% of the time. Consult a coating manufacturer for appropriate coating materials and application methods based on the operating temperature range of the equipment.

5.1.2.2 Carbon Steel All carbon steel operating at a service temperature between 32°F and 300°F or in cycling temperature service where the service temperature is between 32°F and 300°F for more than 20% of the time shall be at a minimum primer coated with an epoxy coating. Consult a coating manufacturer for appropriate coating materials and application methods for the operating temperature range of the equipment.

 


APPENDIX B: DETAILS

The following details are referenced in the text of this guideline by their Figure numbers. The diagrams included in this section are representative of details used within the industry. However, they are not intended to display the only accepted method of installation but to serve as an example of commonly used and acceptable practices.

 

 

Figure 1: DOUBLE LAYERED INSULATION SYSTEM

 

Notes:

• Inner Layer longitudinal joints at 12 and 6 O’clock. Outer layer joints at 3 and 9 O’clock.

• Stagger half round segments on each layer and between the two layers as shown above.

• Use thin coat of sealant over whole joint depth. Butter excess down the face of the joint. Use sealant on outer layer only.


 

 

 

 

Figure 2: TRIPLE LAYERED INSULATION SYSTEM

 

 


 

Figure 3: FULL THICKNESS SHIPLAP ELBOW FITTING

 

Notes:

• Shiplap end cut to thickness “X” to accommodate double layer pipe insulation.

• Use in lieu of double layered fittings.

• Wrap elbow with Vapor Retarder Tape.


 

 

 

 

Figure 4: TAPING PATTERN

 

Notes:

• Use two wraps of tape to insure adequate bond.

• Use nylon or glass filament type tape 3/4” wide.

 

 


 

 

Figure 5: DOUBLE LAYER EXPANSION/CONTRACTION JOINT DETAIL

 

Notes:

• Allow sealant beads to cure prior to installation of outer layer.

• Position outer layer packed glass fiber between sealant dams on inner layer as shown above.

• After glass fiber in contraction joint is installed, insulation sections on either side of contraction joint shall be forced together as tightly as possible.

 


 

 

 

Figure 6: VAPOR STOP DETAILS

 

Notes:

• Mastic should be selected based on the service temperature of the system.

• Mastic shall be sealed to the pipe face and lapped back over the top of the vapor retarder if fitting is left exposed.

 

 

 

Figure 7: DETAIL OF FACTORY APPLIED VAPOR RETARDER

 

Notes:

• Vapor Barrier can be installed using SSL tape as shown above or using liquid adhesives.

• Butt joints to be covered a minimum of 1.5” on each side of joint by vapor retarder tape or butt strip.

 

 

 


 

Figure 8: TANK HEAD INSULATION DETAIL

 

 

 

Notes:

• In multiple layer systems, each layer shall be installed so that the horizontal and vertical joints in that layer are staggered from the corresponding joints in the preceding layer by half the height or width of a full section.

• At joint between wall and head section, the outer layer shall be staggered below the inner layer by the thickness of a single layer.

• Where mastics or sealants are required to bond the insulation sections to the tank head consult the manufacturer’s recommendations on service and application temperatures.

 


Table 1: Insulation Thickness Details

 


 

APPENDIX C: THICKNESS TABLES

The following tables show the insulation thickness necessary to prevent condensation on the outer surface of the insulation system jacketing. In a few cases, the tables also include the insulation thickness necessary to limit the heat gain to a specific value (usually 8 btu/hr-ft2 of outer jacketing surface). These thickness recommendations are solely based on various design conditions that are shown with each table. A number of assumptions are also made, including proper system design and installation. There may be additional factors the tables do not address that could influence the end results. These thickness tables are not meant to replace a proper system design and specification by a qualified design engineer familiar with specific ambient design parameters for a given locality. We recommend you consult a qualified engineer and have them work closely with the contractor, and Dyplast to help insure a properly designed, installed, and long-lasting insulation system. Thickness calculations are performed using the 3E Plus software program that uses heat flow algorithms based on ASTM C680-95. The required insulation thicknesses do not include a safety factor. Actual operating conditions can vary. Consult a design engineer for an appropriate safety factor.


ISO-C1, Outdoors, 90%R.H.

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification.


ISO-C1, Outdoors, 85%R.H.

 

 

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification.


ISO-C1, Outdoors, 80%R.H.

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification.


 

ISO-C1, Outdoors, 80%R.H.

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification


 

ISO-C1, Outdoors, 80%R.H.

 

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification.


 

ISO-C1, Outdoors, 80%R.H.

 

This table is based on ASTM C 680-95 heat transfer algorithms. The suggested insulation thickness values assume proper system design and installation, do not include a safety factor, and are applicable only for the specified scenario. Dyplast recommends that the user consult a qualified design engineer familiar with this type of construction for proper system design and specification.

(Top)

** NOTE TO SPECIFIER ** For more detailed information on installation,